Article Excerpt Abstract: Due to the growing use of non-linear load equipment and new technologies in buildings, harmonic currents generated in distribution systems pose a new problem for electrical engineers. This is a serious problem when power quality is a prime concern. The problem is due to some non-linear loads showing different current waveforms when supplied by a distorted voltage. This paper summarises the results of a case study survey in an office building with a large number of connected computers, a major source of harmonics. The scope of work included site measurement and analyses. The characteristics and effects of harmonic distortion of load current and voltages on distribution systems are discussed. It was found that on most occasions, careful planning and design can minimise the risk of harmonic-related losses in electrical systems. However, this does not always guarantee satisfaction. A bank of capacitors may be used to improve power factors in electrical systems, though in some cases such a bank may make the situation worse. An alternative is filters, but the position of filters is also crucial. Based on the case study, the paper discusses alternatives and provides some practical solutions to the problem of harmonics in office buildings.
Keywords: Computer centres, Harmonic distortion, Office buildings, Power quality
Introduction
The subject of power quality has been given increased attention over the past decade. Broadly defined, power quality refers to the degree to which voltages and currents in a system represent sinusoidal waveforms. Harmonics have become a serious concern for electrical engineers following the wide use of electronic appliances. The quality of electrical power in commercial and industrial installation is undeniably decreasing. In addition to external disturbances, such as outages, sags and spikes due to switching and atmospheric phenomena, there are inherent, internal causes specific to buildings that result from the combined use of linear and non-linear loads. Solid examples of degradation are:
*** Untimely tripping of protection devices
*** Harmonic overloads
*** Voltage and current distortion
*** Temperature rise in conductors and generators
*** Reliability of low-voltage AC systems
The above disturbances are well documented and are directly related to the proliferation of loads consuming non-sinusoidal current, referred to as "non-linear loads" (Singh & Verma, 2007). The harmonic currents generated by non-linear loads cause voltage distortion as they interact with the impedance of electrical distribution systems.
With the increasing use of solid-state circuit equipment, harmonic distortion in supply systems becomes more frequent and severe due to non-linear characteristics of such circuits (Singh & Verma, 2007). Well known non-linear devices include converters, inverters, electronic-ballast, and lifts and especially computer equipment. These voltage or current distortions may cause unsafe and unreliable electrical power supplies, malfunction of equipment, overheating of conductors and can reduce the efficiency, and life of most connected loads (Frewin, 1991; Maza-Ortega, Gomez-Exposito, Trigo-Garcia, & Burgos-Payan, 2005). Therefore, harmonic distortion is an undesirable effect for electrical systems.
"Clean" power refers to voltage and current waveforms that represent pure sine waves and are free of any distortion. "Dirty" power refers to voltage and current waveforms that are distorted and do not represent pure sine waves. Alternating current power supply has always suffered from the effects of harmonics. The harmful effects at the tee-off point, lighting and socket outlet circuits of electrical distribution systems are documented in many publications (Elmoudi, 2006; Newcombe, 1994a).
How Harmonic Distortions are Formed
A harmonic is defined as "a sinusoidal component of a periodic wave or quantity having a frequency that is integral multiples of the fundamental frequency" (IEEE, 1995). Harmonics can be voltage and/or current related and present in an electrical system in multiples of the fundamental frequency. If the fundamental frequency is 50 Hz, the second harmonic is 100 Hz, the...
|
|

More articles from Architectural Science Review
Space planning and energy efficiency in laboratory buildings: the role..., September 01, 2007 Urbanism and cinematography.(Cinematic Urbanism: A History of the Mode..., September 01, 2007 A distinguished Portuguese architect.(Alvaro Siza)(Book review), September 01, 2007 Cities in conflict.(Architects Without Frontiers: War, Reconstruction ..., September 01, 2007 Roman mosaics.(Tunisian Mosaics: Treasures from Roman Africa)(Book rev..., September 01, 2007
Looking for additional articles?
Search our database of over 3 million articles.
Looking for more in-depth information on this industry?
Search our complete database of Industry & Market reports by text, subject, publication
name or publication date.
About Goliath
Whether you're looking for sales prospects, competitive information, company
analysis or best practices in managing your organization,
Goliath can help you meet your business needs.
Our extensive business information databases empower business
professionals with both the breadth and depth of credible,
authoritative information they need to support their business
goals. Whether it be strategic planning, sales prospecting,
company research or defining management best practices -
Goliath is your leading source for accurate information.
|
|